A Diagnostic Method for Moisture Intrusion Fault in OIP Bushing
Article
Article Title | A Diagnostic Method for Moisture Intrusion Fault in OIP Bushing |
---|---|
ERA Journal ID | 979 |
Article Category | Article |
Authors | Liao, Wei (Author), Zhou, Lijun (Author), Wang, Dongyang (Author), Wang, An (Author), Guo, Lei (Author) and Cui, Yi (Author) |
Journal Title | IEEE Transactions on Instrumentation and Measurement |
Journal Citation | 69 (9), pp. 7072-7081 |
Number of Pages | 10 |
Year | 2020 |
Publisher | IEEE (Institute of Electrical and Electronics Engineers) |
Place of Publication | United States |
ISSN | 0018-9456 |
1557-9662 | |
Digital Object Identifier (DOI) | https://doi.org/10.1109/TIM.2020.2976278 |
Web Address (URL) | https://ieeexplore.ieee.org/document/9016085 |
Abstract | Oil-impregnated paper (OIP) bushing is essential equipment in power substations, and moisture intrusion is one of the major faults during its operation. In this article, a method is proposed to diagnose the moisture intrusion fault by the hidden Markov model (HMM) and the shuffled frog-leaping algorithm (SFLA). First, HMM is employed to characterize the probabilistic relationship between the moisture states and frequency-domain spectroscopy (FDS). Then, SFLA is adopted to optimize the locatable results of moisture intrusion point (MIP) in the bushing. Next, extensive simulated data are used for parameter training in the HMM-SFLA model library, with cross-validation for optimal parameters' configuration of HMM and SFLA. Finally, the proposed method was validated by experiment in laboratory and field measurements. The results show that the proposed method can effectively diagnose the MIP of OIP bushings. |
Keywords | Fault diagnosis; frequency-domain spectroscopy (FDS); hidden Markov model (HMM); moisture intrusion point (MIP); oil-impregnated bushing; shuffled frog-leaping algorithm (SFLA) |
ANZSRC Field of Research 2020 | 400803. Electrical energy generation (incl. renewables, excl. photovoltaics) |
Public Notes | Files associated with this item cannot be displayed due to copyright restrictions. |
Byline Affiliations | Southwest Jiaotong University, China |
University of Queensland | |
Institution of Origin | University of Southern Queensland |